Question 1
A technician must select arc-rated protective clothing before working near energized switchgear. According to standard electrical safety practice, the level of PPE required is determined primarily by the:
- System voltage alone, since a higher operating voltage will always demand a greater level of protection
- The incident energy and arc-flash hazard/risk category of the task
- Distance from the nearest exit and the available escape time
- Technician's years of experience working on similar equipment
Show answer & explanation
Correct answer: B - The incident energy and arc-flash hazard/risk category of the task
Question 2
A pressure transmitter is ranged 0-150 psi with a 4-20 mA output. At an applied pressure of 75 psi the technician records an as-found output of 13.6 mA. Expressed in engineering units, the error is:
- 1.6 mA high, which is within normal tolerance for any transmitter
- 10 psi low, because the output is below the expected current
- 1.6 psi high, equal to the milliamp deviation measured
- 15 psi high
Show answer & explanation
Correct answer: D - 15 psi high
Question 3
A technician needs to measure the actual current flowing in an operating 4-20 mA control loop. The meter should be connected:
- In series with the circuit, with the loop energized
- In parallel across the load, with the loop energized
- In series with the circuit, after de-energizing the loop
- In parallel across the transmitter terminals, with power removed
Show answer & explanation
Correct answer: A - In series with the circuit, with the loop energized
Question 4
A Type K thermocouple must be extended from the sensor head back to the transmitter. To avoid introducing measurement error, the extension wire must:
- Be ordinary copper conductor, because copper offers the lowest electrical resistance over the run
- Be any shielded twisted pair rated for the installation voltage
- Have the same thermo-electric properties as the thermocouple (Type KX)
- Match the color of the field wiring used elsewhere in the loop
Show answer & explanation
Correct answer: C - Have the same thermo-electric properties as the thermocouple (Type KX)
Question 5
In a bubbler (dip-tube) level measurement system, a bubble escapes from the bottom of the dip tube at the moment the supplied air pressure becomes:
- Greater than the atmospheric pressure measured at the top of the open tank
- Equal to the hydrostatic head of the liquid above the tube opening
- Independent of the liquid level once flow is established
- Less than the vapor pressure of the process liquid
Show answer & explanation
Correct answer: B - Equal to the hydrostatic head of the liquid above the tube opening
Question 6
While troubleshooting a transmitter that should output 4-20 mA, a technician measures exactly 0 mA at the loop terminals. This reading most likely indicates:
- The process variable is at 0% of the calibrated range
- The transmitter is correctly calibrated at its lower range value
- The process variable has briefly exceeded 100% of span
- An open circuit or loss of loop power
Show answer & explanation
Correct answer: D - An open circuit or loss of loop power
Question 7
A plant trends bearing vibration data to estimate when a pump will require service, scheduling work only when the data indicates developing wear. This approach is best classified as:
- Predictive maintenance
- Preventive maintenance performed on a fixed calendar interval
- Corrective maintenance carried out after a functional failure
- Run-to-failure maintenance with no scheduled intervention
Show answer & explanation
Correct answer: A - Predictive maintenance
Question 8
During a loop check, a technician simulates an increasing measured variable into a transmitter, but the controller indication moves downward instead of upward. The most likely cause is:
- The simulated signal is too small to register on the controller
- The process vessel is empty, so there is no real measurement to display at the controller
- Reversed signal polarity or an incorrect direct/reverse action setting
- The transmitter has not yet reached operating temperature
Show answer & explanation
Correct answer: C - Reversed signal polarity or an incorrect direct/reverse action setting
Question 9
After field-verifying an installation, a technician finds that the routing of a signal cable differs from the design drawing. The correct action is to mark the actual installed condition on the drawing - a practice known as:
- Bench calibrating the affected loop before start-up
- Redlining the documentation to reflect the as-built condition
- Commissioning the loop while it runs under live process conditions
- Decommissioning the cable until the drawing is reissued
Show answer & explanation
Correct answer: B - Redlining the documentation to reflect the as-built condition
Question 10
On a P&ID drawn to ISA-5.1, an instrument bubble is tagged 'FIC'. This identifies the device as a:
- Flow Indicating Controller
- Final Inspection Checkpoint in the loop
- Field Instrument Cabinet location
- Fluid Isolation Component on the line
Show answer & explanation
Correct answer: A - Flow Indicating Controller